Envelope work is the opposite of electrical work. An electrical fault concentrates at a termination, and the camera's job is to compare one small part against its sibling. A building-envelope problem spreads across a surface, so the camera's job is to find a pattern — and a pattern only becomes a finding once a second instrument confirms it. This guide is the envelope process. For distribution equipment, use the electrical panel guide; for assembling the report, use the FLIR Thermal Studio reporting guide.
What a handheld imager can and cannot settle
It can show you that surfaces differ in temperature, and where the differences are: missing insulation, thermal bridging, a wall that is behaving like it is wet, a path where air is moving.
It cannot measure an R-value, cannot confirm moisture, cannot see through a foil-faced assembly or a reflective coating, and cannot tell you the difference between wet insulation and absent insulation on the image alone. Treat every envelope finding as a hypothesis with a location until it is confirmed.
The conditions decide the result
Temperature difference across the assembly. Contrast is driven by the gap between inside and outside. A mild spring afternoon gives you almost nothing; a cold morning on a heated building gives you the pattern in one pass.
Solar loading. A sunlit wall stores heat and keeps releasing it for hours, which both masks real defects and invents false ones. Inspect in shade, early, or well after the sun has left the elevation, and say when you flew it.
Wind. Moving air strips the pattern off an exterior surface through convection. Calm conditions, or an interior survey, are what make an exterior elevation readable.
Pressure difference. Air leakage only shows up when air is actually moving through the assembly. Natural stack effect helps on a cold day; a blower door makes it unambiguous.
Record indoor and outdoor temperature, wind, sun exposure and the time since the elevation lost the sun, once per session, and attach them to the images.
Reading the pattern
- A broad, irregular patch on a wall or ceiling is consistent with missing or wet insulation. It is not a diagnosis until a moisture meter has been on it.
- A repeating linear pattern following framing, studs or slab edges is a thermal bridge — geometry doing what the assembly dictates, not necessarily a defect.
- Streaks at joints, rim joists, outlets and penetrations suggest air leakage paths rather than missing insulation; confirm with a smoke pencil or a pressure reading.
- Cooler at corners and around openings is usually geometry and air movement, and it is normal until it is not — compare against other corners in the same assembly.
- Flat roofs after sunset are the classic case: dry insulation sheds the day's solar gain quickly while wet insulation keeps radiating. A night survey after a clear, sunny day is why that inspection timing exists.
- Glass and low-e coatings reflect the surroundings and read the coating, not the cavity, so vary your angle before you believe anything.
The route
- One wide establishing shot per elevation or room, with a visible reference object for scale and orientation.
- Work the surface in a consistent order, at a fixed distance, with camera settings unchanged for the whole session.
- Image the suspect area and an adjacent normal area in the same frame, so the comparison is inside the picture.
- Note the finding on site: location, conditions, apparent delta-T, what you think it is, what would confirm it.
- Return with the confirming instrument before the finding reaches the report.
Confirming before you write it up
- Moisture — a pin or pinless meter at the exact spot, and note the reading.
- Air leakage — smoke pencil, or a documented pressure difference.
- Missing insulation — pattern consistency across the whole elevation, plus what you know of the assembly from drawings or a borescope.
Then report it as one page per finding: both images, the conditions, the numbers, and a sentence a contractor can act on. Rank by consequence rather than by how dramatic the image looks, and state what you could not inspect and why. The report structure itself is covered in the reporting guide linked at the top.
What we stock
Prices are our live catalog listings; confirm current price and stock on the product page.
How this guide was built
The process here is standard building-envelope thermography; the products and prices come from the live listings in our catalog, checked on November 14, 2026. We have not performed these inspections ourselves, and pattern reading is a hypothesis, not a measurement — the confirming instrument is what makes it a finding. For roof-moisture surveys, your client's standard (commonly ASTM C1153 for insulated flat roofing) governs timing and method.